MRU-105 MRU-106接地电阻测试仪

MRU-105 MRU-106接地电阻测试仪

MRU-105 / 106接地电阻测试仪

指数: 

WMGBMRU105

MRU-105 / 106接地电阻测试仪

指数: 

WMGBMRU105

Earth Resistance and Resistivity Meter

The MRU-105 and MRU-106 (for 60 Hz) are portable meters for the earth resistance and earth resistivity measurement (Wenners method). The instruments can measure resistance using 2, 3, or 4 poles method. Measurements can be simplified using current clamps. The very high immunity for existing interference voltage AC + DC at which measurement is still performed: 24 V (68 V-p-p) but also measurement of existing interference voltage up to 40 V is unique functionality of the meters. Moreover meters measure the resistance of the probes and calculate automatically the error coming from probe's resistances.

指数:

WMGBMRU105

接地电阻和电阻率测试仪

该MRU-105和MRU-106(60赫兹)是接地电阻和接地电阻率测量(Wenners法)便携式仪表。该仪器可使用2个,3个或4极法测量电阻。测量可以使用电流钳进行简化。对于现有的干扰电压的AC+ DC很高免疫力在这仍然是进行测定:现有干扰电压高达40 V24 V(68 V-P-P),而且还测量了米的独特功能。此外米测量探针的阻力并自动计算从探头的电阻来的错误。 

The meters MRU-105 and MRU-106 (for 60 Hz) additionaly can be powered from Ni-MH batteries or standard C size, and the test results can be stored in the internal memory and transmited to PC via USB - cable.

Measurement of earth resistance using a three- or four- pole technique:

?ability to perform measurements of multiple earth system using three-pole

?technique without disconnecting earth system measured (with the application of clamps),

?supervision of the measurement conditions (eg. voltages, impact resistance measurement electrodes RH i RS and battery state/monitor)

?high immunity of interference voltage.

Measurement of ground resistivity (Wenner’s method):

?the earth resistivity measurement with the possibility to introduce the distance between electrodes, automatic calculation and displaying the resistivity.

Measurement of resistance using a two- or four-pole technique.

Built-in battery charger.

Memory for 300 measurement results with an ability to transfer the data to a PC.

Meter meets the requirements of the standard EN 61557.

Electric security:

?type of insulation: double, according to EN 61010 - 1 and IEC 61557

?measurement category: CAT III 300 V acc. to EN 61010 - 1

?protection class acc. to EN 60529: IP54

Other technical data:

?power supply: alkaline batteries LR14 (C) (5 pcs.) or Ni-MH battery package

?charger power supply: 100...250 V, 50...60 Hz

?display: LCD, 20 mm high

Rated operational conditions:

?operating temperature: 0...+40°C

?maximum interference voltage AC + DC, at which the measurement is still performed: 24 V (68 Vp-p)

?test current for resistance value ≤ 100 Ω: 225 mA

?maximum measured voltage: 40 V

?test current frequency: 128 Hz

Measurement of earth resistance:

measurement range in accordance with IEC61557 - 5: 0,12 Ω...20 kΩ

Range    Resolution    Accuracy

0,00...9,99 Ω    0,01 Ω    ±(3% m.v. + 3 digits)

10,0...99,9 Ω    0,1 Ω    ±(2% m.v. + 2 digits)

100...999 Ω    1 Ω    

1,00...9,99 kΩ    0,01 kΩ    

10,0...20,0 kΩ    0,1 kΩ    

Measurement of earth resistance using clamps:

measurement range in accordance with IEC61557 - 5: 0,16 Ω...20 kΩ

Range    Resolution    Accuracy

0,00...9,99 Ω    0,01 Ω    ±(8% m.v. + 3 digits)

10,0...99,9 Ω    0,1 Ω    ±(8% m.v. + 2 digits)

100...999 Ω    1 Ω    

1,00...9,99 kΩ    0,01 kΩ    

10,0...20,0 kΩ    0,1 kΩ    

Measurement of ground resistivity:

Range    Resolution    Accuracy

0,00...9,99 Ωm    0,01 Ωm    ±(3% m.v. + 3 digits)

10,0...99,9 Ωm    0,1 Ωm    ±(2% m.v. + 2 digits)

100...999 Ωm    1 Ωm    

1,00...9,99 kΩm    10 Ωm    

10,0...99,9 kΩm    100 Ωm    

100...999 kΩm    1 kΩm    

?m.v.”- measured value”