上海楹点检测设备有限公司

供应商机

当前所在位置:网站首页 > 供应商机

MZC-304回路阻抗测试表

MZC-304

MZC-304回路阻抗测试表

上海楹点检测设备有限公司产品和服务质量好,性价比高,为您节省采购成本!电子测量仪器:示波器,示波表,电源,频谱仪,温度测试仪,数字电桥,万用表,频闪仪,转速表,功率计,信号发生器,钳形表,电阻测试仪,绝缘电阻测试仪,兆欧表,热像仪........公司承诺,所有商品保证原装正品,一年保修,终身维护!服务热线:151-210-77168/Q


指数: 

WMGBMZC304

Loop Meter

Measurements of impedance in a short circuit loop.

?L-PE circuit,

?L-N, L-L circuit,

?L-PE(RCD) circuit - without tripping the circuit breaker > 30 mA.

Low voltage resistance measurement:

?continuity measurement - DC current +200 mA with wire resistivity reset

?low current resistance measurement with accoustic signalling,

the measurements are posible in instalations 220/380 V, 230/400 V, 240/415 V with frequeency range 45...65 Hz.

memory of 10 banks of 99 cells each (min.10000 records).

Radio wireless interface comunication

Short circuit loop impedance ZL-PE,ZL-N,ZL-L , resistance and reactance measurement

Short circuit loop impedance ZS

Range    Resolution    Accuracy

0,00...19,99 Ω    0,01 Ω    ±(5% m.v. + 3 digits)

20,0...199,9 Ω    0,1 Ω    

200...1999 Ω    1 Ω    

一、nominal work voltage UnL-N / UnL-L: 220/380 V, 230/400 V, 240/415 V,

二、voltage range 180…270 V (for ZL-PE i ZL-N) and 180…460 V (dla ZL-L),

三、nominal network frequency fn: 50 Hz, 60 Hz,

四、frequency range: 45…65 Hz,

五、maximum measurement current 7,6 A for 230 V (3 x 10 ms), 13,3 A for 400 V (3 x 10 ms),

六、PE terminal connection correctness check with the help of touch electrode (ZL-PE, ZL-PE(RCD)),

七、short circuit current calculation for nominal voltage

 

Short circuit loop resistance RS and reactance XS

Range    Resolution    Accuracy

0,00...19,99 Ω    0,01 Ω    ±(5% m.v. + 5 digits) warto?ci ZS

20,0...199,9 Ω    0,1 Ω    

calculated and displayed for ZS<200 Ω

Short circuit loop impedance ZL-PE RCD measurement - without tripping the circuit breaker

Short circuit loop impedance ZS measurement

Range    Resolution    Accuracy

0,00...19,99 Ω    0,01 Ω    ±(6% m.v. + 10 digits)

20,0...199,9 Ω    0,1 Ω    ±(6% m.v. + 5 digits)

200...1999 Ω    1 Ω    

?No RCD reaction for I?n≥30 mA,

?nominal work voltage Un: 220 V, 230 V, 240 V,

?voltage range: 180…270 V,

?nominal network frequency fn: 50 Hz, 60 Hz,

?frequency range: 45…65 Hz,

?PE terminal connection correctness check with the help of touch electrode

?short-circuit current calculation for nominal voltage

Short circuit resistance RS and reactance XS display range (for ZL-PE RCD)*

Range    Resolution    Accuracy

0,00...19,99 Ω    0,01 Ω    ±(6% m.v. + 10 digits) of ZS value

20,0...199,9 Ω    0,1 Ω    ±(6% m.v. + 5 digits) of ZS value

*ocalculated and displayed for Zs<200 Ω

Low voltage resistance measurement

Measurement of continuity of equipotential bondings and protective conductors with ±200 mA current

Range    Resolution    Accuracy

0,00...19,99 Ω    0,01 Ω    ±(2% m.v. + 3 digits)

20,0...199,9 Ω    0,1 Ω    

200...400 Ω    1 Ω    

?open terminals voltage: 4…9 V DC,

?output current at R<2 Ω: min 200 mA (ISC: 200...250 mA),

?test leads resistance compension,

?measurement for both current polarization

Low current resistance measurement

Range    Resolution    Accuracy

0,0...199,9 Ω    0,1 Ω    ±(3% m.v. + 3 digits)

200...1999 Ω    1 Ω    

?open terminals voltage4...9 V DC

?output current ISC< 8 mA,

?accustic signal for measured resistance < 30 Ω ± 50%,

?test leads resistance compensation.

AC voltage measurement

Range    Resolution    Accuracy

0,0 V...299,99 V    0,1 V    ±(2% m.v. + 6 digits)

300 V...500 V    1 V    ±(2% m.v. + 2 digits)

?frequency range 45...65 Hz,

?test result refreshing: twice per second

Frequency measurement

Range    Resolution    Accuracy

45,0 V...65,0 Hz    0,1 Hz    ±(0,1% m.v. + 1 digit)

?voltage range: 50... 500 V

Electrical safety:

?type of insulation: double, according EN 61010, 61557:2007 - 01

?measurement category: III 600 V (CAT IV 300 V)

?protectin class acc. to EN 60529: IP67

Other technical data:

?power supply: package of batteries (AA, 4 pcs.)

?batteries performance (short-circuit loop): min.5000 measurements

Rated operational conditions:

1.operating temperature: 0...+50°C

2.humidity: 20 - 80%

3.rated mains voltage: 220/380 V, 230/400 V, 240/415 V

"m.v. = measured value"



m.yingdian168.b2b168.com